Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR01349

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2006 VIOL - BUILDING SVCS & SYSTEMS Approved
05/15/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Face plates missing on outlet.
TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
***Replace face plate.
05/15/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Multi plug adaptor:
TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
***Replace with an approved fused power strip.
05/15/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical service clearance:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
***Move basket and hardware that are in fromt of the panel.