Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR01349
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
05/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Face plates missing on outlet. TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ***Replace face plate. |
|
05/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Multi plug adaptor: TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ***Replace with an approved fused power strip. |
|
05/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Electrical service clearance: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ***Move basket and hardware that are in fromt of the panel. |