Case: T06FR01326

Parcel: 121120040


Addresses:

5421 E SPEEDWAY BL


Inspection Status: Compliance

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR01326

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
05/24/2006 VIOL - BUILDING SVCS & SYSTEMS Compliance All electrical hazards abated. No extension cords in use. Removed multiplug adapters and acquire power strips with circuit breakers. Electrical panel is accessable and free of obstructions. All power strips have their own power supply ( no more piggy backing ).
05/09/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.4.2 Relocatable power taps shall be directly connected to a permanently installed recepticle. Unplug all powerstrips that are connected in a series to another power strip,
"piggy backing". ( in electronic room, offices, ceiling of the sales floor in NWcorner of store.)
05/09/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.4 Multiplug adapters not complying with ICC Electrical Code are prohibited. Remove adaptors found in storage area and offices.
05/09/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.5 Extenswion cords shall not be used as a aubstitute for permanent wiring. Remove extension cords found in offices and stock areas.
05/09/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.3 No storage of materials shall be located in designated working space in front of electrical service equipment. Remove stored boxes and racks blocking the electric panel in stock room.
05/09/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.1 Identified electrical hazards shall be ebated. Repair damaged cord on coke machine.