Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2006 | VIOL - PRECAUTION AGAINST FIRE | Partial Approval | Isles created in between rolling storage for fuel break. | |
| 05/09/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | IFC 2003 315.2 Storage of combustible materials in buildings shall be orderly. 1.Creat an aisle between rolling storage bins and a 'fuel break' . Maintain 18 inches below sprinkler heads. 2.Organize closet in storage room. 3.Clean/organize wires, power strips/ trash under desks in office area. |
|
| 05/09/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | 315.2.1Storage shall be maintained 18 inches below sprinkler heads in a sprinklered building. Remove storage blocking sprinkler head on E. wall of stock room. |