Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T06FR01287
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2006 | INSP - FULL | Correction Required | 2003 IFC-1008 Back exit door shall have the sign: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. 2003 IFC-605 Open junction box in front south wall, shall replace with cover plate. 2003 IFC-906 Fire extinguisher shall be serviced annually and shall have a current service tag attached. 2003 IFC-904 Automatic fire extinguisher system of commercial cooking equipment shall be serviced with a current service tag attached. 2003 IFC-605 Electrical outlet outside in front shall have a cover plate, wires exposed to the environment. |