Case: T06FR01282

Parcel: 11308012A


Addresses:

3100 N 1ST AV

Inspection Status: Approved

Inspection History: VIOL - FIRE RESIST.RATED CONST

Date Description Inspector Results Comments
05/23/2006 VIOL - FIRE RESIST.RATED CONST Approved
05/09/2006 VIOL - FIRE RESIST.RATED CONST Violation 4). Fire stopping shall be completed in server room. IFC 703.1.1
Doors with closures serving corridors shall be kept closed at all times, as per IFC requirements, which state:

703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.