Case: T06FR01218

Parcel: 11445262E

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR01218

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2006 VIOL - BUILDING SVCS & SYSTEMS Approved
05/08/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical service box clearance:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
***Clear area in fromt of electrical box.


Re-inspection scheduled for 5/23/06. Done 6/26/06.