Inspection History Details
Inspection Status: Continued
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T06FR01216
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Continued
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2006 | VIOL - FIRE PROTECTION SYSTEMS | Continued | extinguishers hung on brackets | |
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (throughout) | |
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.7- Fire extinguishers shall be installed on hangers or brackets. | |
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6- Fire protection systems shall be inspected, tested and maintained in operative conditions at all times. 1. kitchen- escutcheon missing on sprinkler head 2. brewery- string hanging from sprinkler head 3. mechanical- compressed gas cylinders chained to FP system 4. kitchen- deep fryer operations shall be separated from ignition sources by 16" or an 8" high plate |
|
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 903.3- Sprinkler systems shall be designed and installed in accordance with NFPA standards. 1. upstairs- awning over bar is unprotected 2. mechanical- opening to outside unprotected 3. sprinkler head in dining area (south) needs to be extended |
|
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.3- Hoods and ducts shall be cleaned at intervals necessary to prevent the accumulation of grease. Records shall be kept. | |
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.4- Automatic fire extinguishing systems shall be serviced at least every 6 months. | |
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.1- Filters for hood systems shall be in place when in operation. | |
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.3- Minimum size fire extinguisher per table 906.3(1) is 2A. | |
05/04/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.5- A class K rated fire extinguisher is required for cooking equipment using animal or vegetable oils. (within 30' of deep fryer) |