Case Number - T06FR01216
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Continued
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2006 | VIOL - BUILDING SVCS & SYSTEMS | Continued | extension cords removed | |
05/04/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. mechanical room (swamp box) 2. kitchen (through ceiling) 3. dining room (south to neon sign) |
|
05/04/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of 30" width, 36" depth, 78" height shall be provided in front of electrical service equipment. 1. mechanical 2. tool room 3. hallway lockers 4. mechanical upstairs |
|
05/04/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. dining room (south) 2. brewery (ceiling) 3. upstairs by stairwell |
|
05/04/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Electrical hazards shall be abated. 1. flex protector behind deep fryer 2. cord behind bean cooker 3. protective all-weather covers on receptacles upstairs (x 2) |