Case: T06FR01216

Parcel: 11504602D


Addresses:

865 E UNIVERSITY BL

Inspection Status: Continued

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
06/01/2006 VIOL - BUILDING SVCS & SYSTEMS Continued extension cords removed
05/04/2006 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring.
1. mechanical room (swamp box)
2. kitchen (through ceiling)
3. dining room (south to neon sign)
05/04/2006 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of 30" width, 36" depth, 78" height shall be provided in front of electrical service equipment.
1. mechanical
2. tool room
3. hallway lockers
4. mechanical upstairs
05/04/2006 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited.
1. dining room (south)
2. brewery (ceiling)
3. upstairs by stairwell
05/04/2006 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Electrical hazards shall be abated.
1. flex protector behind deep fryer
2. cord behind bean cooker
3. protective all-weather covers on receptacles upstairs (x 2)