Case: T06FR01204

Parcel: 11445262J

Inspection Status: Approved

Inspection History: VIOL - FIRE RESIST.RATED CONST

Case Number - T06FR01204

Inspection Description - VIOL - FIRE RESIST.RATED CONST

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2006 VIOL - FIRE RESIST.RATED CONST Approved
05/05/2006 VIOL - FIRE RESIST.RATED CONST Violation Tires on ceiling:
TFC 703.3 Ceilings. The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly, shall be prohibited.
***Remove same from the ceiling in an approved manner.
05/05/2006 VIOL - FIRE RESIST.RATED CONST Violation Holes in ceiling; missing ceiling tiles:
TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.
***Replace missing tiles [office]; seal holes in an approved manner.