Case: T06FR01066

Parcel: 11445262G

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR01066

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2006 VIOL - BUILDING SVCS & SYSTEMS Approved
04/27/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Yellow extension cord:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
***Remove and replace with approved electrical outlet, or move work area to a location where there is approved power available.
04/27/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Open Electrical Boxes/ holes in service panel:
TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
***Place blanks in Electrical service panel boxes [Fixture room, fixture area, by employees bathroom, and any others that are missing.]
***Remove unused power Boxes in an approved manner. [per the Electrical code, and show proof of same.]
***Cover open wire boxes [fixture area].