Case: T06FR00978

Parcel: 121113250


Addresses:

4865 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR00978

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
05/15/2006 VIOL - MEANS OF EGRESS Approved
04/25/2006 VIOL - MEANS OF EGRESS Violation Front and Back Door:
TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.
*** Place above-mentioned sign on or near front and rear door in an approved manner.

TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
***Remove all bolts on doors. Rear security door may have bolt ONLY if door is unlocked while occupied! Wood bar assembly is also prohibited and must be removed. Thumb-latch type lock only on rear interior door. [No double keyed locks].


Re-inspection scheduled for 5/11/06.

All abated 5/15/06. Will continue to clear shop of excess piles.