Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
IFC 2003 - 1003.6 OBSTUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH OF A MEANS OF EGRESS. ( FOUND ON REINSPECTION) RELOCATE SODA BOXES BLOCKING EXIT WIDTH OF REAR EXIT (FACING NORTH) |
| 03/29/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
IFC 2003 - 1026.3 EXIT SIGNS SHALL BE MAINTAINED AND ILLUMINATED. REPLACE MISSING EXIT SIGN. |
| 03/29/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
IFC 2003 - 1008.1.8.4 SLIDE LOCKS ARE NOT PERMITTED ON AN EXITING DOOR. REMOVE SLIDE LOCK FROM DOOR THAT EXITS TO MAIN LOBBY. |
| 03/29/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
IFC 2003 - 1013.4.1 AISLES SERVING AS PART OF THE EXIT ACCESS SHALL BE MAINTAINED NOT LESS THAN 28 " IN WIDTH. REMOVE STORAGE IN HALLWAY LEADING FROM FOOD PREP AREA TO EXIT IN REAR. |