Case: T06FR00774

Parcel: 13106031B


Addresses:

2545 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR00774

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2006 VIOL - BUILDING SVCS & SYSTEMS Approved
04/12/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cord use:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
*** Replace with approved power strip. [including cord-to-box extension in liquor storage area.
04/12/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Open wiring boxes, exposed wires:
TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
*** Cover all exposed wire ends, splices, and open electrical boxes.
04/12/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical panels:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
*** Clear area from around electrical boxes in an approved manner.
04/12/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Open spaces in circuit breaker panel, ceiling fan, lights:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
*** Have banks placed in panel, so there are no open spaces.
*** Clean and cover, or replace fans in both bathrooms.
*** Replace closet light fixture in an approved manner.