Case: T06FR00728

Parcel: 13316030C

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
05/10/2006 VIOL - MEANS OF EGRESS Approved Exiting issues abated as of 5/9/06.
04/10/2006 VIOL - MEANS OF EGRESS Violation Exit signs not illuminated:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.
***Have all exit signs working.
04/10/2006 VIOL - MEANS OF EGRESS Violation Upstairs exit access blocked:
TFC 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
***Clear the exit access, from the stairwell to the upstairs exit door, and keep it clear.
04/10/2006 VIOL - MEANS OF EGRESS Violation Emergency lighting:
TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area.
***Repair all emergency lighting as needed. [S. exit area]