Case: T06FR00728

Parcel: 13316030C

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
07/11/2006 VIOL - FIRE PROTECTION SYSTEMS Approved This was fixed immediately...logged later.
04/10/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Poor location of fire extinguisher:
TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view.
***Relocate the extinguisher behind the grill, near an escape exit from the area. Place signs to show the location of extinguishers and pull station.
04/10/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Missing screen in hood system:
TFC 901.6 [and TFC 904.11.6] Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
***Replace screen IMMEDIATELY....grease laden vapors allow grease to collect creating an imminent fire hazard.
Note: Your system looks very clean. Good job!
Abated as of 5/9/06.


***All sprinkler heads to be inspected and replaced as neccessary, and all escutcheons properly fitted. [check over east bar, prep room]