Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | This was fixed immediately...logged later. | |
| 04/10/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Poor location of fire extinguisher: TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. ***Relocate the extinguisher behind the grill, near an escape exit from the area. Place signs to show the location of extinguishers and pull station. |
|
| 04/10/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Missing screen in hood system: TFC 901.6 [and TFC 904.11.6] Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ***Replace screen IMMEDIATELY....grease laden vapors allow grease to collect creating an imminent fire hazard. Note: Your system looks very clean. Good job! Abated as of 5/9/06. ***All sprinkler heads to be inspected and replaced as neccessary, and all escutcheons properly fitted. [check over east bar, prep room] |