04/06/2006 | INSP - FULL | Correction Required | 2nd exit blocked during past weekend's performance.over 100 plus people in attendance w/only 1 exit. KFOSTER | |
04/06/2006 | INSP - FULL | Correction Required | TFC- 1011.1 Exit Signs. 1) Unblock exit sign so as to be visible at all times. TFC- 1006.1 Egress Illumination. 2) Install a emergency lite-pak in exit corridor leading out east exit. TFC-1027.3 Maintenance of the means of egress. 3) Maintain a clear path to east exit, nothing stored in corridor. |