Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2006 | VIOL - MEANS OF EGRESS | Approved | Abated as of re-inspection on 4/17/06. | |
| 04/03/2006 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area. ***Supply proof of, or install emergency back up lighting. Re-inspection scheduled for 4/17/06. Re-inspected 4/25/06- All ok. B Cobb |