Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T06FR00620

Parcel: 133369580


Addresses:

70 N HARRISON RD

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS Approved abated as of 4/25/06.
04/17/2006 VIOL - BUILDING SVCS & SYSTEMS Not ready for Inspection Will be ready for this item on 4/24/06. [Has to move security camera wires]
04/03/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical box access:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
***Clear area in front of electrical service box.