Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR00540
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/20/2006 | INSP - FULL | Approved | Inspection complete, final. | |
04/12/2006 | INSP - FULL | Not ready for Inspection | ||
03/29/2006 | INSP - FULL | Correction Required | 2003 IFC-1008 Shall post the sign that reads, THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. 2003 IFC-3003.3.3 Commpress gas cylenders shall be secured tp prevent falling. 2003 IFC-904 Automatic fire extinguisher of commercial cooking equipment shall be serviced at least every 6-months. 2003 IFC-904.2.1 K-rated portable fire extinguisher shall have a service tag to show when it was serviced.This is serviced annually. 2003IBC 110 The Certificate of Occupancy shall be posted next to the business license. |