Case: T06FR00469

Parcel: 13408277H


Addresses:

8323 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/27/2006 INSP - FULL Approved all approved. Thank you.
03/27/2006 INSP - FULL Violation 1). Current annual fire alarm inspection report shall be submitted and all repairs shall be corrected. TFC 901.6
2) Currently both local smoke detectors in kitchen area have no batteries. These shall have shall be functioning IFC 901.6
3). Car battery is exposed in parking lot. This shall be disposed of properly. IFC 2703.9.2
4). Heat detectors shall be included in report. IFC 901.6
5). 30-day inspection shall be done on all portable fire extinguishers. IFC 901.6
6). Certificate of occupancy shall be posted. IFC 102.3
7). Remove all obstructions from pull stations. IFC 901.6
8). Exit light out of service in 3-year-old room. IFC 1026. 3
9) Outside mech. room shall be open for reinspection.