Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2006 | INSP - FULL | Approved | All violations complete, final inspection. | |
| 04/20/2006 | INSP - FULL | Continued | ||
| 03/21/2006 | INSP - FULL | Correction Required | IFC-2003 605.5 Extension cords shall not be substitute for permanent wiring. IFC2003-906.1 Need a class K rated portable fire extinguisher in the kitchen. IFC-903- Commercial hood system extinguisher system needs to be serviced.with cuurent service tag. IBC - 110 Certificate of Occupancy needs to be posted next to the business license. |