Case: T06FR00431

Parcel: 127030030


Addresses:

1060 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
07/31/2006 VIOL - BUILDING SVCS & SYSTEMS Approved
03/20/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cord use:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
*** Replace with approved power strip.
03/20/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Decorative lights held with staples, empty sockets, fan, splices:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
*** 1. Place bulbs in ALL empty sockets. [multiple]
*** 2. Take down string of lights held up by staples. May be hung if done in a way approved by the manufactor.
*** 3. No splices allowed unless done in approved manner and concealed in an electrical box. [multiple]
*** 4. Cover fan in office.
03/20/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Hood system:
[M] 610.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code.
***1. Have all hood systems checked and serviced, and proof of same delivered to Fire Marshal.
***2. Replace missing screens over fryer.
NOTE: Make sure this area is working properly AND has adequate fire coverage, AND is charged with fire suppressing agent. Do not continue use of fryer until approved by the Fire Marshal.