Inspection History Details
Inspection Status: Approved
Inspection History: INSP - REINSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2006 | INSP - REINSPECTION | Approved | ||
| 07/03/2006 | INSP - REINSPECTION | Partial Approval | 6/30/06 - Gas bottles secure; All extension cords replaced; Has estimates for electrical outlet in DR. | |
| 06/08/2006 | INSP - REINSPECTION | Violation | On 6/8/06 pre-citation was served to Dahlia Sanchez for failure to comply with most of the above. NOTE: Correction to last inspection: Hood system is not acceptable! Extension cords are still in use! Failure to abate electrical hazards. Hard copy in TFD office. Has until 6/16/06 to comply or will be cited. |
|
| 05/10/2006 | INSP - REINSPECTION | Partial Approval | The following are approved as of 5/9/06: Emergency lighting Bulbs in sockets No splices Hood system checked and screen replaced. K class extinguisher Extinguishers tagged Sprinklers checked [Mar 2006] These points remain to be finished: Secure gas cylinders Replace extension cord with power strip behind bar. Fan cover Elecric outlet for lights installed by professional. [No temporary cords, splices, no passing thru walls.] Pull station signs. |