Inspection History Details
Inspection Status: Partial Approval
Inspection History: INSP - FULL
Case Number - T06FR00399
Inspection Description - INSP - FULL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/29/2006 | INSP - FULL | Partial Approval | All IFC completed. The IBC 110 Cof O is referred to Steve Long. | |
03/15/2006 | INSP - FULL | Correction Required | 2003 TFC-904.11.6.5 The commercial system hood system needs to be serviced 2003 TFC-904 The portable fire extinguisher needs service. TFC-605 Exposed light bulb in the freezer needs the bulb cover. 2003 TFC- 605.3 Open junction box on east wall. TFC-110 Cof O shall be posted next to the business license. |