Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR00389
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2006 | INSP - FULL | Approved | all ok. approved |
|
03/15/2006 | INSP - FULL | Violation | 1). Current sprinkler test and inspection report shall be submitted to TFD, and all repairs shall be corrected. In the following buildings Pre school and O'rielly Building. IFC 901.6 2). Extension cord shall be removed room front entrance.. IFC 605.1 |
|
03/15/2006 | INSP - FULL | Violation | 3). All fire doors with door closures shall remain closed as per. IFC 703.2.2, which states: 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position. |