Case: T06FR00384

Parcel: 117130420


Addresses:

101 S STONE AV

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/14/2006 INSP - FULL Violation 1). Automatic fire sprinkler test and inspection report shall be submitted to TFD, and repairs shall be made before reinspection date. IFC 901.6
2). Remove wooden décor from around sprinkler piping. IFC 901.6
3). Doors with door closures shall be not blocked open. IFC 703.2.2
703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.
703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
4). Exit light out of service Floor 2 ½- IFC 1027
5). Basement: All combustible material shall be removed 30 inches from all electrical service. IFC 605.3 states:

605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.


6). J-BOX needs cap. IFC 605.1
7). Remove clamp from sprinkle piping. IFC 901.6