Case: T06FR00345

Parcel: 12611157A


Addresses:

4445 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
05/31/2006 VIOL - MEANS OF EGRESS Approved
03/13/2006 VIOL - MEANS OF EGRESS Violation Front doors:
TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
The sign shall be in letters 1 inch (25 mm)
high on a contrasting background.
*** Place above-mentioned sign on or near front doors in an approved manner. [both doors please]
03/13/2006 VIOL - MEANS OF EGRESS Violation Bolt and Bar on rear door:
1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter.
*** Remove bolt and wood bar, and hardware, from door.
Note: bolt hardware welded in place; manager agreed not to use, and assumes responsibility for illegal use.