Case: T06FR00345

Parcel: 12611157A


Addresses:

4445 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
05/31/2006 VIOL - FIRE PROTECTION SYSTEMS Approved
03/13/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Pull station for extinguishing agent:
TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.
*** Place an approved sign showing location of pull station.
03/13/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Fire extinguishers.
TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times.
*** Have all extinguishers inspected and tagged in an approved manner.