Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T06FR00333

Parcel: 125091980

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR00333

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2006 INSP - FULL Approved all ok
03/10/2006 INSP - FULL Violation 1). The material that covers the entire material on side of corridor is of an unknown material. Info from manufacturer shall be given to TFD. This is under IFC 805.1
805.1 General. In occupancies of Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall be flame resistant in accordance with Section 805.2 and NFPA 701 or be noncombustible.
805.2 Acceptance criteria and reports. Where required to be
flame resistant, decorative materials shall be tested by an approved
agency and pass Test 1, as described in NFPA 701, or
such materials shall be noncombustible. Reports of test results
shall be prepared in accordance with NFPA 701 and furnished
to the fire code official upon request.

Or material must be removed
2). Fire alarm test results shall be submitted to TFD. Currently power light on enunciator panel is out of service. IFC 901.6

3). 30-day inspection shall be done on extinguishers. IFC 901.6