Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR00333
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2006 | INSP - FULL | Approved | all ok | |
03/10/2006 | INSP - FULL | Violation | 1). The material that covers the entire material on side of corridor is of an unknown material. Info from manufacturer shall be given to TFD. This is under IFC 805.1 805.1 General. In occupancies of Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall be flame resistant in accordance with Section 805.2 and NFPA 701 or be noncombustible. 805.2 Acceptance criteria and reports. Where required to be flame resistant, decorative materials shall be tested by an approved agency and pass Test 1, as described in NFPA 701, or such materials shall be noncombustible. Reports of test results shall be prepared in accordance with NFPA 701 and furnished to the fire code official upon request. Or material must be removed 2). Fire alarm test results shall be submitted to TFD. Currently power light on enunciator panel is out of service. IFC 901.6 3). 30-day inspection shall be done on extinguishers. IFC 901.6 |