Case: T06FR00332

Parcel: 11628001L

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR00332

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2006 INSP - FULL Approved approved
03/10/2006 INSP - FULL Violation 1). 6th floor housekeeping: Holes in walls IFC 701.3
2). Ceiling tiles shall be installed in Salon storage. IFC 701
3). Basement: Ceiling tiles missing in banquet storage. IFC 701
4). All doors with door closures shall remain closed as per IFC, which states…
703.2.2 Hold-open devices and closers. Hold-open devices
and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.
703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
5). Plastic cart is blocking laundry chute operation. IFC 901.6
Remove cart.
6). Air handler Room. All combustible materials shall be removed from air handler room. IFC 315.2.3
7). Extension cord shall be removed from store room off breakfast kitchen. IFC 605
8). Lunch Kitchen: Loose nozzle from hood system shall be repaired. IFC 901.6