Case: T06FR00276

Parcel: 12101005A


Addresses:

6161 E PIMA ST


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR00276

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2006 VIOL - FIRE PROTECTION SYSTEMS Approved
05/24/2006 VIOL - FIRE PROTECTION SYSTEMS Partial Approval
03/03/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Fire Extinguishers and sprinklers:
TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
***1. All extinguishers shall be inspected and tagged in accordance with this code.
*** 2. All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.
[ 10 escutcheons in library, 2 in weight room, 11 in laundry room, and 10 in pool room.] Also check sprinkler in the closet of pool room to be in an approved condition.