Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE RESIST.RATED CONST
Case Number - T06FR00276
Inspection Description - VIOL - FIRE RESIST.RATED CONST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2006 | VIOL - FIRE RESIST.RATED CONST | Approved | ||
03/03/2006 | VIOL - FIRE RESIST.RATED CONST | Violation | Sprinkler head open spaces & hole in maint. office ceiling: TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. *** Eliminate open spaces in ceiling in an approved manner. [ 10 escutcheons in library, 2 in weight room, 11 in laundry room, and 10 in pool room.] |