Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR00263
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 03/02/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. *** Remove or replace with approved electrical strip, all extension cords. 1. located by front door 2. located by cash register [2] 3. located in office |
|
| 03/02/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Tape covering electrical switches: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. *** Remove tape from circuit breaker switches, allowing them to "break" in the event of overload. |
|
| 03/02/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Electric service box: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment *** Keep electric service/ circuit breaker box clear in an approved manner. |