Case: T06FR00263

Parcel: 12102089A


Addresses:

5501 E PIMA ST


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR00263

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/06/2006 VIOL - BUILDING SVCS & SYSTEMS Approved
03/02/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
*** Remove or replace with approved electrical strip, all extension cords.
1. located by front door
2. located by cash register [2]
3. located in office
03/02/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Tape covering electrical switches:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
*** Remove tape from circuit breaker switches, allowing them to "break" in the event of overload.
03/02/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Electric service box:
TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment
*** Keep electric service/ circuit breaker box clear in an approved manner.