Case: T06FR00258

Parcel: 12108034A


Addresses:

6171 E BELLEVUE ST

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
03/01/2006 VIOL - PRECAUTION AGAINST FIRE Approved BBQ proximity to building:
308.3.1 Open-flame cooking devices. Charcoal burners and other open-flame cooking devices shall not be operated on combustible balconies or within 10 feet (3048 mm) of combustible construction.
*** Both built in gas grills to be removed from present location. [Cease use immediately]
[currently located 4 inches from stucco wall and less than 1 foot from dry tree, and under wood overhang]
*** BBQ outside unit 16 to be removed. [from under balcony]
*** BBQ owned by unit 14 occupants to be removed.
03/01/2006 VIOL - PRECAUTION AGAINST FIRE Violation Gasoline and combustion engine in Apt. 1:
305.1 Clearance from ignition sources. Clearance between
ignition sources, such as light fixtures, heaters and flame-producing
devices, and combustible materials shall be maintained
in an approved manner.
304.2 Storage. Storage of combustibles shall not produce conditions that will create a nuisance or a hazard to the public health, safety or welfare.
[note: found gasoline can outside unit 1, under stairwell approx. 2 weeks ago. 1 week later found gas can and minibike chained under stairwell outside unit 1. Contacted manager both times. On 3/1/06 while doing inspection saw gas can and minibike inside unit 1. Tenant removed both immediately.]
*** Advise all tenants it is unlawful to store gasoline, or combustion vehicles and engines, in apartments or under stairwells, and these must be stored, or kept, in a safe and approved manner.

Re-inspection set for 3/17/06.
Re-inspected 4/25/06 All violations abated, new large address installed. Good job. B Cobb