Case: T06FR00239

Parcel: 12701005D


Addresses:

5151 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T06FR00239

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2006 INSP - FULL Approved all ok
02/28/2006 INSP - FULL Violation 1). Fire sprinkler test and inspection report shall be submitted to Tucson fire Department, all required repairs shall be completed. IFC 901.6
2). Fire pump operational test report shall be submitted to Tucson fire Department, all required repairs shall be completed. IFC 901.6
3). Fire alarm test inspection report shall be submitted to Tucson fire Department, all required repairs shall be completed. IFC 901.6
4). Fire drill shall be conducted. Date to be determined by 3-25-06. IFC 404.2.
5). Copy of generator testing shall be submitted. IFC 604.3.2
6). Elevator room- remove boxes and trash. IFC 315.2.3
7). Suite 750- Ceiling tiles shall be replaced, Currently missing. IFC 701
8). Suite 750- Doors with door closures shall always remain closed. IFC 703.2.2
9). Suite 280- properly mount fire extinguisher as per the following requirements;

906.5 Conspicuous location. Extinguishers shall be located in Conspicuous locations where they will be readily accessible
and immediately available for use. These locations shall be
along normal paths of travel, unless the fire code official determines
that the hazard posed indicates the need for placement
away from normal paths of travel.
906.6 Unobstructed and unobscured. Fire extinguishers
shall not be obstructed or obscured from view. In rooms or areas
in which visual obstruction cannot be completely avoided,
means shall be provided to indicate the locations of
extinguishers.
906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be securely
anchored to the mounting surface in accordance with the
manufacturer's installation instructions.

10). 7th floor office- File cabinet is near collapse. This shall be replaced. IFC 304.2
11). Suite 900- ceiling tiles shall be repaired of replaced. IFC 701
12). 8th floor lobby- Lamp is blocking safety sign near elevator, shall be removed. IFC 607.2
13). 8th floor-exit sign out of service.