Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR00230
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | All abated. | |
| 03/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Partial Approval | Items abated: Light fixtures, Electrical panel access. | |
| 02/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1 [Wiring of lights and electrical boxes]: Abatement of electrical hazards. Identified electrical hazards shall be abated. All outlets and lights must be wired in accordance with the approved Electrical Code. Please provide proof of compliance. [front window electrical source on east room, west room ceiling lights, fans electrical source box over west front door.] |
|
| 02/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3 [Electrical panel access]: Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. *** Clear door to, and space in front of, electrical service box. |
|
| 02/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5 [Extension cord use]: Extension cords and flexible cords shall not be a substitute for permanent wiring. *** Remove all extension cords used for permanant wiring and replace with approved wiring, or power strip. [cash register, front east window lighting] |