Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T06FR00230

Parcel: 12102089A


Addresses:

5527 E PIMA ST


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR00230

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS Approved All abated.
03/20/2006 VIOL - BUILDING SVCS & SYSTEMS Partial Approval Items abated: Light fixtures, Electrical panel access.
02/27/2006 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1 [Wiring of lights and electrical boxes]:
Abatement of electrical hazards. Identified electrical hazards shall be abated.
All outlets and lights must be wired in accordance with the approved Electrical Code. Please provide proof of compliance. [front window electrical source on east room, west room ceiling lights, fans electrical source box over west front door.]
02/27/2006 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3 [Electrical panel access]:
Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
*** Clear door to, and space in front of, electrical service box.
02/27/2006 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5 [Extension cord use]:
Extension cords and flexible cords shall not be a substitute for permanent wiring.
*** Remove all extension cords used for permanant wiring and replace with approved wiring, or power strip.
[cash register, front east window lighting]