Case: T06FR00086

Parcel: 127022690


Addresses:

5324 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
02/27/2006 VIOL - PRECAUTION AGAINST FIRE Approved These 3 items OK as of 2/27/06
01/26/2006 VIOL - PRECAUTION AGAINST FIRE Violation Sprinklers:

TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.

Please note: [Kitchen] Remove all items higher than 18 inches below sprinkler head level.
01/26/2006 VIOL - PRECAUTION AGAINST FIRE Violation Dumpsters:
304.3.3 Capacity exceeding 1.5 cubic yards. Dumpsters and containers with an individual capacity of 1.5 cubic yards (40.5 cubic feet) (1.15 m3) or more shall not be stored in buildings or placed within 5 feet (1524 mm) of combustible walls, openings or combustible roof eave lines.

Please move dumpsters away from building in accordance with this provision, and place "stops" to prevent reoccurance.
01/26/2006 VIOL - PRECAUTION AGAINST FIRE Violation General Housekeeping:
304.1 Waste accumulation prohibited. Combustible waste
material creating a fire hazard shall not be allowed to accumulate
in buildings or structures or upon premises.

Please remove trash, and clutter from 1. Power and Communication room, and 2. Laundry room, and laundry room closet.