Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2006 | VIOL - PRECAUTION AGAINST FIRE | Approved | These 3 items OK as of 2/27/06 | |
| 01/26/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | Sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Please note: [Kitchen] Remove all items higher than 18 inches below sprinkler head level. |
|
| 01/26/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | Dumpsters: 304.3.3 Capacity exceeding 1.5 cubic yards. Dumpsters and containers with an individual capacity of 1.5 cubic yards (40.5 cubic feet) (1.15 m3) or more shall not be stored in buildings or placed within 5 feet (1524 mm) of combustible walls, openings or combustible roof eave lines. Please move dumpsters away from building in accordance with this provision, and place "stops" to prevent reoccurance. |
|
| 01/26/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | General Housekeeping: 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Please remove trash, and clutter from 1. Power and Communication room, and 2. Laundry room, and laundry room closet. |