Case: T06FR00081

Parcel: 12605025A


Addresses:

4024 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/03/2006 INSP - FULL Approved Approved.
01/25/2006 INSP - FULL Correction Required TFC- 505.1 Address Numbers
1) Address the Building according to the Pima County Address Display Requirements left.
01/25/2006 INSP - FULL Correction Required TFC- 605.1 Electricial Hazards
2) Replace black & white extension cords leading over front counter with UL/ FM approved power-taps with over current protection.
3) Do the same for cord under the stairs.
01/25/2006 INSP - FULL Correction Required TFC-906.1 Fire Protection Systems
4) Service portable fire extinguisher, should be done once a year. Mount in a permant location.