Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2006 | INSP - FULL | Correction Required | 2003 TFC-1008.1.8.3 Front entrance door . Shall have the sign stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. tfc-901.6 Fire extinguishers shall be serviced annually and shall have a current service tag attached. TFC-1008.1.9 Emergency back up lights shall be in good working order and shall illuminated when tested. TFC-904.11.5 Hood system: Commercial cooking equipment shall be seviced at least every 6- months, sprinkler heads shall be replaced annually have maintains records and show proof. |