Case: T06FR00010

Parcel: 14042085A


Addresses:

2570 E VALENCIA RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/01/2006 INSP - FULL Approved
01/05/2006 INSP - FULL Correction Required 2003 TFC-904.11.5 Cooking equipment involving vegetable or animal fat shall be protected by a class K rated portable fire extinguisher with in 30 feet.
2003TFC-904.11.6.4 Automatic fire extinguisher system of commercial-tpye cooking equipment shall be serviced every 6 months. Maintain records and show proof.
TFC-904.11.6.3 Cleaning hood duct system from the roof down to the hood system shall be done by a company that is qualified every 6 months or when the grease is built up on the duct works.
TFC-904.11.6.5 Fire extinguisher shall be serviced annually and shall have a current service tag attached.
TFC-605.3 Damage cover for light in the freezer,shall be replaced.