Case: T06FR00008

Parcel: 117170110


Addresses:

135 S 6TH AV


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR00008

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2006 VIOL - FIRE PROTECTION SYSTEMS Approved all ok
01/05/2006 VIOL - FIRE PROTECTION SYSTEMS Violation 1). Because of deep-frying, a Class K extinguisher shall be required.
The IFC states:

904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.