Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T06FR00003
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2006 | VIOL - MEANS OF EGRESS | Approved | ||
01/13/2006 | VIOL - MEANS OF EGRESS | Violation | 2. TFC 1006.1 Concerning all exits: Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Order: All exit sign to be in working order, and clearly visible. |
|
01/13/2006 | VIOL - MEANS OF EGRESS | Violation | 3. TFC 1011.1 Exit Signs: Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Order: An additional exit sign shall be placed approx. over the counter area, so as to be visible from the North East showroom area, pointing toward the main entry. |
|
01/04/2006 | VIOL - MEANS OF EGRESS | Violation | 1. TFC 1008.1.8.3 ** A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. Order: Place above mentioned sign , in an approved manner, at the front main door. |