Permit: T06EL02428

Parcel: 13728019B


Addresses:

890 W MELRIDGE ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/07/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT TERMINATE 2 #4 WIRES UNDER SAME LUG, GROUNDING.
2. STRAP #4 TO WALL OF HOUSE.
02/26/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO COMPLIANCE NOTE #2
02/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. PANEL NOT RATED FOR OUTDOOR USE
2. BOND WATER & GAS PIPING