Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DOG IN YARD LOCK UP DOG RECALL INSP. |
|
| 01/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. REVISE PERMIT TO SHOW THIS IS A DUPLEX WITH SEPARATE UNIT NUMBERS AND METERS AND INSTALL UNIT NUMBERS ON UNITS. 2. USE A LISTED GUY KIT FOR MAST SUPPORT AND SECURE IT INTO STRUCTURE - NOT SHEETING NEC 230.28 3. FEEDER ENTERING W.P BOX ABOVE SERVICE NEEDS PROPER CONNECTOR - NEC 314 4. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE AND/OR BURY 12" MINIMUM - NEC 250.54 & 300.5 |