Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02421

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED TO RECEIVE TUSD AND UNDERGROUND INSPECTION REPORTS
04/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
04/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDED CONDUCTOR NOT TO BOND TO PANEL ENCLOSURE -- NEC 250.24 A5 (2005 NEC)
2. WHERE IS SECONDE GROUND ROD? ALL UNDERGROUND TO LIGHTING COVERED WITHOUT INSPECTION, NEED PLANS.

NOTE: SECOND GROUND ROD LOCATED IN HAND HOLE BOX, TO BE DRIVEN ALL THE WAY AND METAL ENCLOSURES, RACEWAYS TO BE MADE ELECTRICALLY CONTINUOUS FOR GROUNDING ELECTRODE CONDUCTOR - NEC 250.64(E) ALSO, GROUND RODS TO BE 6' MINIMUM APART.
04/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEUTRAL AFTER 1ST DISCONNECTING MEANS TO BE UNBONDED
2. INSTALL REJECTION PINS
3. TIGHTEN LOOSE LOCKNUT SERVICE NIPPLE & RISER
4. LABEL BREAKERS
5. PROTECT CONDUCTORS FROM SHARP METAL EDGES OF NIPPLES
6. SUPPORT GROUNDING ELECTRODE CONDUCTOR
7. NO PLANS ON SITE
8. UNCOVER AREAS COVERED WITHOUT INSPECTION
9. OPEN PULL BOX FOR INSPECTION - NOTE: SPLICES NEED TO BE FOR WET LOCATION.

PLEASE PAY REFEE

* CALLED AND WAITED FOR CONTACT PERSON -- NO SHOW

NEED TO MEET WITH ELECTRICIAN
03/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
03/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
JASON 404-1743

1. GROUND ROD COVER W/O INSPECTION
2. RISER BOND WIRE TOO SMALL, NEED #4 WIRE PER 250.66
3. NIPPLE BETWEEN METER AND MAIN DISCONNECT TO BE #4
4. 2/0 COPPER ONLY GOOD FOR 175A
5. NIPPLE BETWEEN DISCON & PANEL NEEDS #6 BECAUSE OF FUSES.
6. DID ANYONE INSPECT UNDERGROUND & WHERE IS PLAN
FOR JOB - THIS PERMIT IS FOR ELECT. PEDESTAL FOR STREET LTS, HOWEVER, THIS IS A SERVICE FOR PARKING LOT LIGHTING - A PLAN IS NEEDED? APPROVED PLAN THRU DEVELOPMENT SERVICES.
02/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SERVICE INSPECTION ONLY
1. SERVICE NEEDS SECOND GROUND ROD - NEC 250.56
2. BURY GROUNDING ELECTRODE CONDUCTOR
3. BOND SERVICE RISER - NEC 250.92
4. BOND SERVICE NIPPLE - NEC 250.92
5. INSTALL SERVICE CONDUCTORS AND PANEL FEEDERS
6. IDENTIFY SERVICE DISCONNECT - NEC 230.70 B
7. NIPPLE DISCONNECT TO PANEL TO BE GROUNDED -
NEC 250.122
8. BOND NEUTRAL TO DISCONNECT ENCLOSURE - NEC 250.24B
9. TOP OF GUTTER TO BE RAINTITE - NEC 110 AND APPEARS TO BE UNDERSIZED -- NEC 314.28
02/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :$
1) COULD NOT LOCATE SERVICE