Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL02421
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO RECEIVE TUSD AND UNDERGROUND INSPECTION REPORTS |
|
04/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
04/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDED CONDUCTOR NOT TO BOND TO PANEL ENCLOSURE -- NEC 250.24 A5 (2005 NEC) 2. WHERE IS SECONDE GROUND ROD? ALL UNDERGROUND TO LIGHTING COVERED WITHOUT INSPECTION, NEED PLANS. NOTE: SECOND GROUND ROD LOCATED IN HAND HOLE BOX, TO BE DRIVEN ALL THE WAY AND METAL ENCLOSURES, RACEWAYS TO BE MADE ELECTRICALLY CONTINUOUS FOR GROUNDING ELECTRODE CONDUCTOR - NEC 250.64(E) ALSO, GROUND RODS TO BE 6' MINIMUM APART. |
|
04/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEUTRAL AFTER 1ST DISCONNECTING MEANS TO BE UNBONDED 2. INSTALL REJECTION PINS 3. TIGHTEN LOOSE LOCKNUT SERVICE NIPPLE & RISER 4. LABEL BREAKERS 5. PROTECT CONDUCTORS FROM SHARP METAL EDGES OF NIPPLES 6. SUPPORT GROUNDING ELECTRODE CONDUCTOR 7. NO PLANS ON SITE 8. UNCOVER AREAS COVERED WITHOUT INSPECTION 9. OPEN PULL BOX FOR INSPECTION - NOTE: SPLICES NEED TO BE FOR WET LOCATION. PLEASE PAY REFEE * CALLED AND WAITED FOR CONTACT PERSON -- NO SHOW NEED TO MEET WITH ELECTRICIAN |
|
03/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
03/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* JASON 404-1743 1. GROUND ROD COVER W/O INSPECTION 2. RISER BOND WIRE TOO SMALL, NEED #4 WIRE PER 250.66 3. NIPPLE BETWEEN METER AND MAIN DISCONNECT TO BE #4 4. 2/0 COPPER ONLY GOOD FOR 175A 5. NIPPLE BETWEEN DISCON & PANEL NEEDS #6 BECAUSE OF FUSES. 6. DID ANYONE INSPECT UNDERGROUND & WHERE IS PLAN FOR JOB - THIS PERMIT IS FOR ELECT. PEDESTAL FOR STREET LTS, HOWEVER, THIS IS A SERVICE FOR PARKING LOT LIGHTING - A PLAN IS NEEDED? APPROVED PLAN THRU DEVELOPMENT SERVICES. |
|
02/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE INSPECTION ONLY 1. SERVICE NEEDS SECOND GROUND ROD - NEC 250.56 2. BURY GROUNDING ELECTRODE CONDUCTOR 3. BOND SERVICE RISER - NEC 250.92 4. BOND SERVICE NIPPLE - NEC 250.92 5. INSTALL SERVICE CONDUCTORS AND PANEL FEEDERS 6. IDENTIFY SERVICE DISCONNECT - NEC 230.70 B 7. NIPPLE DISCONNECT TO PANEL TO BE GROUNDED - NEC 250.122 8. BOND NEUTRAL TO DISCONNECT ENCLOSURE - NEC 250.24B 9. TOP OF GUTTER TO BE RAINTITE - NEC 110 AND APPEARS TO BE UNDERSIZED -- NEC 314.28 |
|
02/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :$ 1) COULD NOT LOCATE SERVICE |