Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/07/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR 3 3/0 COPPER CONDUCTORS FOR SERVICE CONDUCTORS - INSTALL PER PLAN OR REVISE PLAN. 2. BACK FED BREAKERS TO BE SECURED TO PANEL PER NEC 408.16 3. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3 4. NEED TO BOND GAS & WATER PIPING PER NEC 250.104 AT BOTH BUILDINGS 5. BOND SERVICE MAST PER NEC 250.96 & 250.102 6. INSTALL GROUNDING ELECTRODES AT 2ND STRUCTURE PER NEC 250.32 & 250.50 7. NEUTRAL & GROUND CONDUCTORS #6 AND SMALLER TO BE CONTINUOUSLY MARKED PER NEC 200.6 & 250.119 |