Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 01/16/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. BE ADVISED THAT PER 230.24 NEC, SERVICE CONDUCTORS OVER ROOFS MUST BE 8' MIN. 2. RISER CONDUIT BRACE MUST BE A LISTED ASSY. TYPE HOMEMADE OUT OF SMASHED EMT NOT APPROVED. 3. VERIFY GAS BOND TO INSPECTOR 4. OK TO 2 GROUND RODS & WATER PIPE BOND 5. CONSULT WITH TEP ABOUT ROOF CLEARANCE FOR SERVICE DROP. |