Permit: T06EL02396

Parcel: 112034130

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/26/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/24/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) UNIT #19 ONLY: BATH GFI'S NOT WORKING
2) OPEN BULB TYPE FIXTURE NOT ALLOWED IN CLOTHES CLOSET
3) ALL SWITCHES TO BE GROUNDED
4) SMOKE DETECTORS NOT WORKING/NOT INTERCONNECTED AND NEED DETECTOR IN BEDROOM
5) TIGHTEN ALL LOOSE DEVICES, HAVE UPSIDE DOWN SWITCH
6) PROVIDE GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES
7) INSTALL RANGE RECEPTACLE COVER AND DISPOSAL RECEPTACLE COVER
8) MAX LENGTH OF DISPOSAL CORD IS 36" MAX FOR DISHWASHER CORD IS 48" TIGHTEN DISHWASHER CORD CONNECTOR
9) MICROWAVE TO BE ON DEDICATED BRANCH CKT (DRAWS 15 AMPS)
10) RECEPTACLES TO BE FLUSH WITH FACE PLATE AND SECURE
11) PANEL DIRECTORY NOT CORRECTLY IDENTIFIED THROUGH 60 UNITS