Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/09/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY HOWARD |
|
| 01/08/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS 2) NEW GROUNDING ELECTRODE SYSTEM-FINISH 3) USE AN ANTIOXIDE COMPOUND WITH ALL ALUMINUM CONDUCTORS-ALSO INSTALL ALL STRANDS 4) TIGHTEN LOOSE FITTINGS 5) USE PROPER SUPPORT HARDWARE FOR PANEL AND RISER 6) A PERMANENT METAL ADDRESS LABEL IS NEEDED 7) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH NON COMBUSTIBLE PRODUCT |
|
| 12/26/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* NO WORK DONE AT THIS TIME |