Permit: T06EL02389

Parcel: 134170210


Addresses:

7215 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/26/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/09/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY HOWARD
01/08/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS
2) NEW GROUNDING ELECTRODE SYSTEM-FINISH
3) USE AN ANTIOXIDE COMPOUND WITH ALL ALUMINUM CONDUCTORS-ALSO INSTALL ALL STRANDS
4) TIGHTEN LOOSE FITTINGS
5) USE PROPER SUPPORT HARDWARE FOR PANEL AND RISER
6) A PERMANENT METAL ADDRESS LABEL IS NEEDED
7) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH NON COMBUSTIBLE PRODUCT
12/26/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
NO WORK DONE AT THIS TIME