Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BRACE TO BE SECURED BY MEANS OTHER THAN WATER CLAMP 2) WHERE IS RECEPTACLE FOR KITCHEN COUNTERS AS DISCUSSED 3) IF ITEMS NOT CORRECTED WITHIN 10 DAYS POWER MAY BE RECINDED |
|
| 12/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/18/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED KITCHEN RECEPTACLES. 2. RECEPTACLES AND WIRING TO BE IN JUNCTION BOXES 3. EXTENDER BOXES NEEDED AT COMBUSTIBLES 4. WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM. 5. INSTALL SMOKE DETECTORS AS PER MANUFACTURE INSTRUCTIONS. 6. FILL UNUSED OPENINGS IN PANEL 7. USE BREAKERS LISTED BY MANUFACTURES 8. SECURE PANEL COVER 9. BRACES FOR RISER ARE NON-EFFECTIVE |