Permit: T06EL02384

Parcel: 11107179B


Addresses:

2740 N SPARKMAN BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BRACE TO BE SECURED BY MEANS OTHER THAN WATER CLAMP
2) WHERE IS RECEPTACLE FOR KITCHEN COUNTERS AS DISCUSSED
3) IF ITEMS NOT CORRECTED WITHIN 10 DAYS POWER MAY BE RECINDED
12/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/18/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED KITCHEN RECEPTACLES.
2. RECEPTACLES AND WIRING TO BE IN JUNCTION BOXES
3. EXTENDER BOXES NEEDED AT COMBUSTIBLES
4. WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM.
5. INSTALL SMOKE DETECTORS AS PER MANUFACTURE INSTRUCTIONS.
6. FILL UNUSED OPENINGS IN PANEL
7. USE BREAKERS LISTED BY MANUFACTURES
8. SECURE PANEL COVER
9. BRACES FOR RISER ARE NON-EFFECTIVE